Floor-standing design Purpose for data centers Number of phases (input-output) 3-3 General characteristics Nominal power, kVA 30 Input Nominal voltage 220/380, 230/400, 240/415 VAC (3 phases, 4 wires + ground) Voltage range 305–478 VAC (full load); 228–478 VAC (70% load) Total harmonic distortion of current No more than 2% Power factor Over 0.99 Frequency 40–70 Hz Output Voltage 220/380, 230/400, 240/415 VAC Voltage 24 V DC (3 phase, 4 wires + ground) Total Harmonic Distortion Max. 1.5% with linear load, max. 4% with non-linear load Voltage Regulation Range ±1% (static) Frequency 50/60 Hz Overload Capacity Up to 105% on: continuous operation; Over 105 to 110% on: 60 min; Over 110 to 125% on: 10 min; Over 125 to 150% on: 1 minute; Over 150%: 1 second Battery Nominal Voltage ±240 VDC (default, adjustable from ±180 to ±276 VDC); Charging Voltage - ±272 VDC 204V to 312V DC (Adjustable from 204V to 312V) Charging Time 14 minutes (UPS at 70% load with internal battery strings.) Charging Current 15A Communication Interfaces Standard Output Dry Contact x 4, Input Dry Contact x 2, Parallel Port x 2, USB Port x 1, RS232 Port x 1, Remote Emergency Power Off Port x 1, Mini-Card Slot x 2 Efficiency AC-AC Conversion Over 96% (Peak Efficiency) ECO Mode 99% Indication LCD 5" Touch Screen Others Parallel Redundancy and Expansion Up to 4 pcs. Operating Conditions Operating Temperature 0–40°C Relative Humidity 0–95% (non-condensing) Noise Level Less than 56 dB Dimensions and Weight of the UPS Weight 100 kg Conforming to Standards Safety and EMC CE, RCM (IEC62040-1, Class C2 according to IEC62040-2); Protection Class - IP20 (standard); IP42 (optional for long-term redundancy)